Audit calculation assumptions
- Safety factor: `1.25` - Peak sun hours: `4.5` - PV performance factor: `0.8` - Battery depth of discharge: `0.9` - PV recovery reserve: `1.25` - Backup target hours: `8`
Use this when you need detailed reference information for Audit.
Defaults
- Safety factor:
1.25 - Peak sun hours:
4.5 - PV performance factor:
0.8 - Battery depth of discharge:
0.9 - PV recovery reserve:
1.25 - Backup target hours:
8
All assumptions are editable per audit.
Load item calculations
- Total watts = quantity × watts per unit
- Daily energy Wh = total watts × runtime hours
- Day energy Wh = total watts × day runtime hours
- Night energy Wh = total watts × night runtime hours
- Estimated surge watts = total watts × surge factor
Audit totals
- Total running load counts inverter-backed load items.
- Estimated surge load sums inverter-backed item surge values.
- Daily, day, and night energy demand sum all load items.
- Critical and non-critical load watts split items by critical status.
- Recommended inverter kW = larger of safety-adjusted running load or estimated surge load, divided by 1000.
- Recommended battery kWh = critical load watts × backup target hours × safety factor ÷ battery depth of discharge ÷ 1000.
- Recommended solar kWp = daily energy demand × PV recovery reserve ÷ peak sun hours ÷ PV performance factor ÷ 1000.
Generated findings
The system creates unresolved findings for:
- audit not linked to a CRM record
- missing wattage
- missing runtime
- zero quantity
- high surge factor
- battery recommendation below night load requirement
- missing solar assumption inputs such as peak sun hours
Resolved system findings are retained historically. If the same issue still exists after a later calculation refresh, a new unresolved finding can be generated.